Section 4 Design for vertical escape – buildings other than flats

Design for vertical escape - buildings other than flats

  1. Introduction
    1. Number of escape stairs
      1. Mixed use buildings
        1. Single escape stairs
          1. Single escape stairs in small premises
          2. Provision of refuges
            1. Communication
              1. Evacuation lifts
                1. Width of escape stairs
                2. Calculation of minimum stair width
                  1. General
                    1. Discounting of stairs
                      1. Simultaneous evacuation
                        1. Phased evacuation
                        2. Protection of escape stairs
                          1. General
                            1. Enclosure of escape stairs
                              1. Small Premises
                                1. Access lobbies and corridors
                                  1. Separation of adjoining stairways
                                    1. Use of space within protected stairways
                                      1. External walls of protected stairways
                                        1. Gas service pipes in protected stairways
                                        2. Basement stairs
                                          1. External escape stairs

                                            Introduction

                                            4.1An important aspect of means of escape in multi-storey buildings is the availability of a sufficient number of adequately sized and protected escape stairs. This Section deals with escape stairs and includes measures necessary to protect them in all types of building.

                                            The limitation of distances of horizontal travel for means of escape purposes means that most people should be able independently to reach the safety of a protected escape route or final exit. However, some people, for example those who use wheelchairs, may not be able to use stairways without assistance. For them evacuation involving the use of refuges on escape routes and either assistance down (or up) stairways, or the use of suitable lifts, will be necessary.

                                            This Section should be read in conjunction with the general provisions in Section 5.

                                            Number of escape stairs

                                            4.2The number of escape stairs needed in a building (or part of a building) will be determined by:

                                            • athe constraints imposed in item 3 on the design of horizontal escape routes;
                                            • bwhether independent stairs are required in mixed occupancy buildings (see paragraph 4.4);
                                            • cwhether a single stair is acceptable (see paragraphs 4.5 and 4.6); and
                                            • dprovision of adequate width for escape (see paragraph 4.15) while allowing for the possibility that a stair may have to be discounted because of fire or smoke (see paragraph 4.20).

                                            4.3In larger buildings, provisions for access for the Fire and Rescue Service may apply, in which case, some escape stairs may also need to serve as firefighting stairs. The number of escape stairs may therefore be affected by provisions made in Section 17, paragraphs 17.8 and 17.9.

                                            Mixed use buildings

                                            4.4Where a building contains storeys (or parts of storeys) in different purpose groups, it is important to consider the effect of one risk on another. A fire in a shop, or unattended office, could have serious consequences on, for example, a residential or hotel use in the same building. It is therefore important to consider whether completely separate routes of escape should be provided from each different use within the building or whether other effective means to protect common escape routes can be provided.

                                            Single escape stairs

                                            4.5Provided that independent escape routes are not necessary from areas in different purpose groups in accordance with paragraph 2.50 or 4.4, the situations where a building (or part of a building) may be served by a single escape stair are:

                                            • afrom a basement which is allowed to have a single escape route in accordance with paragraph 3.5b and Table 2;
                                            • bfrom a building (other than small premises, see 4.5c) which has no storey with a floor level more than 11m above ground level and in which every storey is allowed to have a single escape route in accordance with paragraph 3.5b and Table 2;
                                            • cin the case of small premises (see paragraph 3.32), in situations where the guidance in paragraph 4.6 is followed.

                                            Single escape stairs in small premises

                                            4.6A single escape stair may be used from:

                                            • asmall premises as described in paragraph 3.33;
                                            • ban office building comprising not more than five storeys above the ground storey, provided that:
                                              • ithe travel distance from every point in each storey does not exceed that given in Table 2 for escape in one direction only; and
                                              • iievery storey at a height greater than 11m has an alternative means of escape;
                                            • ca factory comprising not more than:
                                              • itwo storeys above the ground storey (if the building, or part of the building, is of low risk); or
                                              • iione storey above the ground storey (if the building, or part of the building, is of normal risk); provided that the travel distance from every point on each storey does not exceed that given in Table 2 for escape in one direction only; or
                                            • dprocess plant buildings with an occupant capacity of not more than 10.

                                            Provision of refuges

                                            Diagram 20

                                            4.7Refuges are relatively safe waiting areas for short periods. They are not areas where disabled people should be left alone indefinitely until rescued by the fire and rescue service, or until the fire is extinguished.

                                            A refuge should be provided for each protected stairway affording egress from each storey, except storeys consisting exclusively of plant rooms.

                                            Notes:Whilst a refuge should be provided for each stairway, they need not necessarily be located within the stair enclosure but should enable direct access to the stair. The number of refuge spaces need not necessarily equal the sum of the number of wheelchair users who can be present in the building. Refuges form a part of the management plan and it may be that more than one disabled person will use a single refuge as they pass through as a part of the evacuation procedure.

                                            4.8The following are examples of satisfactory refuges:

                                            • a an enclosure such as a compartment (see Diagram 20), protected lobby, protected corridor or protected stairway (see Diagram 21); and
                                            • ban area in the open air such as a flat roof, balcony, podium or similar place which is sufficiently protected (or remote) from any fire risk and provided with its own means of escape.

                                            4.9Each refuge should provide an area accessible to a wheelchair of at least 900mm x 1400mm in which a wheelchair user can await assistance. Where a refuge is a protected stairway or protected lobby or protected corridor, the wheelchair space should not reduce the width of the escape route. Where the wheelchair space is within a protected stairway, access to the wheelchair space should not obstruct the flow of persons escaping.

                                            4.10Refuges and evacuation lifts should be clearly identified by appropriate fire safety signs. Where a refuge is in a lobby or stairway the sign should be accompanied by a blue mandatory sign worded "Refuge - keep clear".

                                            Communication

                                            4.11To facilitate the effective evacuation of people from refuges an emergency voice communication (EVC) system should be provided. It is essential that the occupants of each refuge are able to alert other people that they are in need of assistance and for them to be reassured that this assistance will be forthcoming.

                                            4.12The EVC system should comply with BS 5839-9:2003 and consist of Type B outstations which communicate with a master station located in the building control room (where one exists) or adjacent to the fire alarm panel.

                                            4.13In some buildings it may be more appropriate to use an alternative approach such as the use of wireless technology.

                                            Evacuation lifts

                                            4.14Guidance on the use of lifts when there is a fire is given in paragraph 5.39.

                                            Width of escape stairs

                                            Table 6

                                            4.15The width of escape stairs should:

                                            • abe not less than the width(s) required for any exit(s) affording access to them;
                                            • bconform with the minimum widths given in Table 6;
                                            • cnot exceed 1400mm if their vertical extent is more than 30m, unless it is provided with a central handrail (see Notes 1 and 2); and
                                            • dnot reduce in width at any point on the way to a final exit.
                                              Note: The 1400mm width has been given for stairs in tall buildings because research indicates that people prefer to stay within reach of a handrail when making a prolonged descent, so much so that the centre part of a wider stair is little used and could be hazardous. Thus additional stair(s) may be needed.
                                              Note: Where a stair wider than 1400mm is provided with a central handrail, then the stair width on each side of the central handrail needs to be considered separately for the purpose of assessing stair capacity.

                                            4.16If the resultant width of the stair is more than 1800mm, then for reasons of safety in use the guidance in Approved Document K Protection from falling, collision and impact is that, in public buildings, the stair should have a central handrail. In such a case see Note 2 to paragraph 4.15.

                                            4.17Where an exit route from a stair also forms the escape from the ground and/or basement storeys, the width may need to be increased accordingly. (See paragraph 3.23).

                                            Calculation of minimum stair width

                                            General

                                            4.18Every escape stair should be wide enough to accommodate the number of persons needing to use it in an emergency. This width will depend on the number of stairs provided and whether the escape strategy for the building (or part of the building) is based on simultaneous evacuation see (paragraph 4.22) or phased evacuation see (paragraph 4.26).

                                            4.19As with the design of horizontal escape routes, where the maximum number of people needing to use the escape stairs is not known, the occupant capacity should be calculated on the basis of the appropriate floor space factors. Guidance for this is set out in Appendix C.

                                            Discounting of stairs

                                            p>4.20Whether phased or simultaneous evacuation is used, where two or more stairs are provided it should be assumed that one of them might not be available due to fire. It is therefore necessary to discount each stair in turn in order to ensure that the capacity of the remaining stair(s) is adequate for the number of persons needing to escape. The stair discounting rule applies to a building fitted with a sprinkler system.

                                            4.21Two exceptions to the above discounting rules are if the escape stairs:

                                            • aare protected by a smoke control system designed in accordance with BS EN 12101-6:2005.
                                            • bare approached on each storey through a protected lobby (a protected lobby need not be provided on the topmost storey for the exception still to apply).

                                            Notes:Paragraph 4.34 identifies several cases where stairs need lobby protection. In such cases the likelihood of a stair not being available is significantly reduced and it is not necessary to discount a stair. However, a storey exit still needs to be discounted, see paragraph 3.21. See also paragraph 4.27 for additional guidance on the potential need to discount stairs in tall buildings utilising phased evacuation.

                                            Simultaneous evacuation

                                            Table 7

                                            4.22In a building designed for simultaneous evacuation, the escape stairs (in conjunction with the rest of the means of escape) should have the capacity to allow all floors to be evacuated simultaneously. In calculating the width of the stairs account is taken of the number of people temporarily housed in the stairways during the evacuation.

                                            4.23Escape based on simultaneous evacuation should be used for:

                                            • aall stairs serving basements;
                                            • ball stairs serving buildings with open spatial planning; and
                                            • call stairs serving Other Residential or Assembly and Recreation buildings.

                                            Notes:BS 5588-7:1997 includes designs based on simultaneous evacuation.

                                            4.24Where simultaneous evacuation is to be used, the capacity of stairs of widths from 1000 to 1800mm is given in Table 7.

                                            4.25As an alternative to using Table 7, the capacity of stairs 1100mm or wider (for simultaneous evacuation) can be derived from the formula:

                                            P = 200w + 50 (w - 0.3)(n - 1), or

                                            w = P + 15n - 15

                                            150 + 50n

                                            where:

                                            (P) is the number of people that can be served;

                                            (w) is the width of the stair, in metres; and (n) is the number of storeys served.

                                            Notes:Stairs with a rise of more than 30m should not be wider than 1400mm unless provided with a central handrail (see paragraph 4.15).
                                            Separate calculations should be made for stairs/flights serving basement storeys and those serving upper storeys.
                                            The population 'P' should be divided by the number of available stairs.
                                            The formula is particularly useful when determining the width of stairs serving a building (or part of a building) where the occupants are not distributed evenly - either within a storey or between storeys.
                                            In the formula, the first part [200w] represents the number of persons estimated to have left the stair after 2.5 minutes of evacuation. The second part [50(w-0.3)(n-1)] represents the number of persons estimated to be accommodated on the stair after this time.

                                            Phased evacuation

                                            Table 8

                                            4.26Where it is appropriate to do so, it may be advantageous to design stairs in high buildings on the basis of phased evacuation. In phased evacuation the first people to be evacuated are all those of reduced mobility and those on the storey most immediately affected by the fire. Subsequently, if there is a need to evacuate more people, it is done two floors at a time. It is a method which cannot be used in every type of building and it depends on the provision (and maintenance) of certain supporting facilities such as fire alarms. It does however enable narrower stairs to be incorporated than would be the case if simultaneous evacuation were used and has the practical advantage of reducing disruption in large buildings.

                                            4.27In tall buildings over 30m in height, where phased evacuation is adopted, there is a potential that persons attempting to escape could be impeded by firefighters entering and operating within the building. This potential varies with the height of the building and with the number of escape stairs that are available. Generally, this can be addressed by incorporating special management procedures into the evacuation strategy in consultation with Fire and Rescue Service. However, in some very tall buildings, typically those over 45m in height, physical measures may need to be incorporated into the building (e.g. by discounting a stair or by some other suitable means).

                                            4.28Phased evacuation may be used for any building provided it is not identified in paragraph 4.23 as needing simultaneous evacuation.

                                            4.29The following criteria should be satisfied in a building (or part of a building) that is designed on the basis of phased evacuation:

                                            • athe stairways should be approached through a protected lobby or protected corridor at each storey, except a top storey;
                                            • bthe lifts should be approached through a protected lobby at each storey (see paragraph 5.42);
                                            • cevery floor should be a compartment floor;
                                            • dif the building has a storey with a floor over 30m above ground level, the building should be protected throughout by an automatic sprinkler system in accordance with paragraph 0.16.
                                            • ethe building should be fitted with an appropriate fire warning system, conforming to at least the L3 standard given in BS 5839-1:2002; and
                                            • fan internal speech communication system should be provided to permit conversation between a control point at fire and rescue service access level and a fire warden on every storey. In addition, the recommendations relating to phased evacuation provided in BS 5839-1 should be followed. Where it is deemed appropriate to install a voice alarm, this should be in accordance with BS 5839-8:1998.

                                            4.30The minimum width of stair needed when phased evacuation is used is given in Table 8. This table assumes a phased evacuation of the fire floor first followed by evacuation of not more than two floors at a time.

                                            Protection of escape stairs

                                            Diagram 22

                                            General

                                            4.31Escape stairs need to have a satisfactory standard of fire protection if they are to fulfil their role as areas of relative safety during a fire evacuation. The guidance in paragraphs 4.32 to paragraph 4.33 should be followed to achieve this.

                                            Enclosure of escape stairs

                                            4.32Every internal escape stair should be a protected stairway (i.e. it should be within a fire-resisting enclosure).

                                            However an unprotected stair (e.g. an accommodation stair) may form part of an internal route to a storey exit or final exit, provided that the distance of travel and the number of people involved are very limited. For example, small premises (described in paragraph 3.32, 4.6 and 4.33) and raised storage areas (see paragraphs 7.7 and 7.8).

                                            There may be additional measures if the protected stairway is also a protected shaft (where it penetrates one or more compartment floors, see Section 8) or if it is a firefighting shaft (see Section 17).

                                            Small Premises

                                            4.33A stair in a small premises, which is not a bar or restaurant, may be open if it does not connect more than two storeys and delivers into the ground storey not more than 3m from the final exit (see Diagrams 22 and 23) and either :

                                            • athe storey is also served by a protected stairway; or
                                            • bit is a single stair in a small premises with the floor area in any storey not exceeding 90m2 and, if the premises contains three storeys, the stair serving either the top or bottom storey is enclosed with fire-resisting construction at the ground storey level and discharges to a final exit independent of the ground storey (see Diagram 23).

                                            Access lobbies and corridors

                                            4.34There are situations where an escape stair needs the added protection of a protected lobby or protected corridor. These are:

                                            • awhere the stair is the only one serving a building (or part of a building) which has more than one storey above or below the ground storey (except for small premises covered in paragraph 4.6a); or
                                            • bwhere the stair serves any storey at a height greater than 18m; or
                                            • cwhere the building is designed for phased evacuation (see paragraph 4.29a).
                                            • dwhere the stair is a firefighting stair.

                                            Lobbies are also needed where the option in paragraph 4.21(b) has been used so as not to discount one stairway when calculating stair widths.

                                            An alternative that may be considered in (a) to (c) above is to use a smoke control system as described in paragraph 4.21(a).

                                            4.35A protected lobby should be also provided between an escape stairway and a place of special fire hazard. In this case, the lobby should have not less than 0.4m2 permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.

                                            4.36 Every protected stairway should discharge:

                                            • adirectly to a final exit; or
                                            • b by way of a protected exit passageway to a final exit.

                                            Notes:: Any such protected exit passageway should have the same standard of fire resistance and lobby protection as the stairway it serves. The exit from a protected stairway should meet the provisions in paragraphs 5.30 to 5.34.

                                            Separation of adjoining stairways

                                            4.37Where two protected stairways are adjacent, they and any protected exit passageways linking them to final exits, should be separated by an imperforate enclosure.

                                            Use of space within protected stairways

                                            4.38A protected stairway needs to be free of potential sources of fire. Consequently, facilities that may be incorporated in a protected stairway are limited to the following:

                                            • asanitary accommodation or washrooms, so long as the accommodation is not used as a cloakroom. A gas water heater or sanitary towel incinerator may be installed in the accommodation but not any other gas appliance;
                                            • b a lift well may be included in a protected stairway, if it is not a firefighting stair;
                                            • ca reception desk or enquiry office area at ground or access level, if it is not in the only stair serving the building or part of the building. The reception or enquiry office area should not be more than 10m2 in area; and/or
                                            • dcupboards enclosed with fire-resisting construction, if it is not in the only stair serving the building or part of the building.

                                            External walls of protected stairways

                                            4.39The external enclosures to protected stairways should meet the provisions in paragraph 5.24.

                                            Gas service pipes in protected stairways

                                            4.40Gas service and installation pipes or associated meters should not be incorporated within a protected stairway unless the gas installation is in accordance with the requirements for installation and connection set out in the Pipelines Safety Regulations 1996, SI 1996 No 825 and the Gas Safety (Installation and Use) Regulations 1998 SI 1998 No 2451. (See also paragraph 8.40.)

                                            Basement stairs

                                            4.41Because of their situation, basement stairways are more likely to be filled with smoke and heat than stairs in ground and upper storeys. Special measures are therefore needed in order to prevent a basement fire endangering upper storeys.

                                            These are set out in the following two paragraphs.

                                            4.42If an escape stair forms part of the only escape route from an upper storey of a building (or part of a building) it should not be continued down to serve any basement storey. The basement should be served by a separate stair.

                                            4.43If there is more than one escape stair from an upper storey of a building (or part of a building), only one of the stairs serving the upper storeys of the building (or part) need be terminated at ground level. Other stairs may connect with the basement storey(s) if there is a protected lobby, or a protected corridor between the stair(s) and accommodation at each basement level.

                                            External escape stairs

                                            Diagram 24

                                            4.44If more than one escape route is available from a storey (or part of a building), some of the escape routes from that storey or part of the building may be by way of an external escape stair, provided that:

                                            • athere is at least one internal escape stair from every part of each storey (excluding plant areas);
                                            • bin the case of an Assembly and Recreation building, the route is not intended for use by members of the public; or
                                            • cin the case of an Institutional building, the route serves only office or residential staff accommodation.

                                            4.45Where external stairs are acceptable as forming part of an escape route, they should meet the provisions in paragraph 5.25.

                                            • 1 Gallery floors with no alternative exit Diagram 1 Gallery floors with no alternative exit
                                            • 2 Flat where all habitable rooms have direct access to an entrance hall Diagram 2 Flat where all habitable rooms have direct access to an entrance hall
                                            • 3 Flat with restricted travel distance from furthest point to entrance Diagram 3 Flat with restricted travel distance from furthest point to entrance
                                            • 4 Flat with an alternative exit but where all habitable rooms have no direct acess to an entrance hall Diagram 4 Flat with an alternative exit but where all habitable rooms have no direct access to an entrance hall
                                            • 5 Multi-storey flat with alternative exits from each habitable room except at entrance level 5 Multi-storey flat with alternative exits from each habitable room except at entrance level
                                            • 6 Multi-storey flat with protected entrance hall and landing Diagram 6 Multi-storey flat with protected entrance hall and landing
                                            • 7 Flats served by one common stair,png Diagram 7 Flats served by one common stair
                                            • 8 Flats served by more than one common stair 8 Flats served by more than one common stair
                                            • 9 Common escape route in small single stair building Diagram 9 Common escape route in small single stair building
                                            • 10 Travel distance in dead-end condition 10 Travel distance in dead-end condition
                                            • 11 Alternative escape routes 11 Alternative escape routes
                                            • 12 Inner room and access room 12 Inner room and access room
                                            • 13 Exits in a central core Diagram 13 Exits in a central core
                                            • 14 Open Connections Diagram 14 Open Connections
                                            • 15 Merging flows at final exit Diagram 15 Merging flows at final exit
                                            • 16 Subdivision of corridors Diagram 16 Subdivision of corridors
                                            • 17 Dead-end corridors Diagram 17 Dead-end corridors
                                            • 18 Maximum travel distances in a small two or three storey premises with a single protected stair to each storey Diagram 18 Maximum travel distances in a small two or three storey premises with a single protected stair to each storey
                                            • 19 Progressive horizontal evacuation in care homes Diagram 19 Progressive horizontal evacuation in care homes
                                            • 20 Refuge formed by compartmentation Diagram 20 Refuge formed by compartmentation
                                            • 21 Refuge formed in a protected stairway Diagram 21 Refuge formed in a protected stairway
                                            • 22 Max travel distance in a small three storey premises with a single stair to each storey Diagram 22 Max travel distance in a small three storey premises with a single stair to each storey
                                            • 23 Max travel distance in a small two storey premises with a single open stair Diagram 23 Max travel distance in a small two storey premises with a single open stair
                                            • 24 External protection to protected stairways Diagram 24 External protection to protected stairways
                                            • 25 Fire resistance of areas adjacent to external stairs 25 Fire resistance of areas adjacent to external stairs
                                            • 26 Lighting diffuser in relation to ceiling Diagram 26 Lighting diffuser in relation to ceiling
                                            • 27 Layout restrictions on Class 3 plastic roofflights TP-b rooflights and TP b lighting diffusers Diagram 27 Layout restrictions on Class 3 plastic rooflights TP-b rooflights and TP b lighting diffusers
                                            • 27a Layout restrictions on small Class 3 plastic rooflights TP b rooflights and lighting diffusers Diagram 27a Layout restrictions on small Class 3 plastic rooflights TP b rooflights and lighting diffusers
                                            • 28 Compartment floors illustration of guidance in paragraph 8.16 Diagram 28 Compartment floors illustration of guidance in paragraph 8.16
                                            • 29 Compartment walls and compartment floors with reference to relevant paragraphs in Section 8 Diagram 29 Compartment walls and compartment floors with reference to relevant paragraphs in Section 8
                                            • 30 Junction of compartment wall with roof Diagram 30 Junction of compartment wall with roof
                                            • 31 Protected shafts Diagram 31 Protected shafts
                                            • 32 Uninsulated glazed screen separating protected shaft from lobby or corridor Diagram 32 Uninsulated glazed screen separating protected shaft from lobby or corridor
                                            • 33 Provisions for cavity barriers Diagram 33 Provisions for cavity barriers
                                            • 34 Cavity wall excluded from provisions for cavity barriers Diagram 34 Cavity wall excluded from provisions for cavity barriers
                                            • 35 Fire-resisting ceiling below concealed space Diagram 35 Fire-resisting ceiling below concealed space
                                            • 36 Provisions for cavity barriers in double-skinned insulated roof sheeting Diagram 36 Provisions for cavity barriers in double-skinned insulated roof sheeting
                                            • 37 Pipes penetrating structure Diagram 37 Pipes penetrating structure
                                            • 38 Enclosure for drainage or water supply pipes Diagram 38 Enclosure for drainage or water supply pipes
                                            • 39 Flues penetrating compartment walls or floors Diagram 39 Flues penetrating compartment walls or floors
                                            • 40 Provisions for external surfaces or walls Diagram 40 Provisions for external surfaces or walls
                                            • 41 Relevant boundary Diagram 41 Relevant boundary
                                            • 42 Notional boundary Diagram 42 Notional boundary
                                            • 43 Status of combustible surface material as unprotected area Diagram 43 Status of combustible surface material as unprotected area
                                            • 44 Unprotected areas which may be disregarded in assessing the separation distance from the boundary Diagram 44 Unprotected areas which may be disregarded in assessing the separation distance from the boundary
                                            • 45 The effect of a canopy on separation distance Diagram 45 The effect of a canopy on separation distance
                                            • 46 Permitted unprotected areas in small residential buildings Diagram 46 Permitted unprotected areas in small residential buildings
                                            • 47 Limitations on spacing and size of plastic rooflights having a Class 3 or Class D-s3 d2 or TP b lower surface Diagram 47 Limitations on spacing and size of plastic rooflights having a Class 3 or Class D-s3 d2 or TP b lower surface
                                            • 48 Example of building footprint and perimeter Diagram 48 Example of building footprint and perimeter
                                            • 49 Relationship between buildings and hardstanding access roads for high reach fire appliances Diagram 49 Relationship between buildings and hardstanding access roads for high reach fire appliances
                                            • 50 Turning facilities Diagram 50 Turning facilities
                                            • 51 Provision of firefighting shafts Diagram 51 Provision of firefighting shafts
                                            • 52 Components of a firefighting shaft Diagram 52 Components of a firefighting shaft
                                            • 53 Fire-resisting construction for smoke outlet shafts Diagram 53 Fire-resisting construction for smoke outlet shafts
                                            • C1 Measurement of door width Diagram C1 Measurement of door width
                                            • C2 Cubic capacity Diagram C2 Cubic capacity
                                            • C3 Area Diagram C3 Area
                                            • C4 Height of building Diagram C4 Height of building
                                            • C5 Number of storeys Diagram C5 Number of storeys
                                            • C6 Height of top storey in buildingC6 Height of top storey in building Diagram C6 Height of top storey in building
                                            • C7 Free area of smoke ventilators Diagram C7 Free area of smoke ventilators
                                            • D1 Classification of Purpose Groups Diagram D1 Classification of Purpose Groups
                                            • E1 Recessed car parking areas Diagram E1 Recessed car parking areas
                                            • Table 1 Limitations on distance of travel in common areas of blocks of flats - see par 2.23 Table 1 Limitations on distance of travel in common areas of blocks of flats - see par 2.23
                                            • Table 2 Limitations on travel distance Table 2 Limitations on travel distance
                                            • Table 3 Minimum number of escape routes and exits from a room tier or storey Table 3 Minimum number of escape routes and exits from a room tier or storey
                                            • Table 4 Widths of escape routes and exits Table 4 Widths of escape routes and exits
                                            • Table 5 Maximum distances of travel in small premises with a protected stair Table 5 Maximum distances of travel in small premises with a protected stair
                                            • Table 6 Minimum widths of escape stairs Table 6 Minimum widths of escape stairs
                                            • Table 7 Capacity of a stair for basements and for simultaneous evacuation of the building Table 7 Capacity of a stair for basements and for simultaneous evacuation of the building
                                            • Table 8 Minimum width of stairs designed for phased evacuation Table 8 Minimum width of stairs designed for phased evacuation
                                            • Table 9 Provisions for escape lighting Table 9 Provisions for escape lighting
                                            • Table 10 Classification of linings Table 10 Classification of linings
                                            • Table 11 Limitations applied to thermoplastic rooflights and lighting diffusers in suspended ceilings and Class 3 plastic rooflights Table 11 Limitations applied to thermoplastic rooflights and lighting diffusers in suspended ceilings and Class 3 plastic rooflights
                                            • Table 12 Maximum dimensions of building or compartment - non-residential buildings Table 12 Maximum dimensions of building or compartment - non-residential buildings
                                            • Table 13 Maximum dimensions of cavities in non-domestic buildings - purpose Groups 2-7 Table 13 Maximum dimensions of cavities in non-domestic buildings - purpose Groups 2-7
                                            • Table 14 Maximum nominal internal diameter of pipes passing through a compartment wall-floor - see par 10.5 onwards Table 14 Maximum nominal internal diameter of pipes passing through a compartment wall-floor - see par 10.5 onwards
                                            • Table 15 Permitted unprotected areas in small buildings or compartments Table 15 Permitted unprotected areas in small buildings or compartments
                                            • Table 16 Limitations on roof coverings Table 16 Limitations on roof coverings
                                            • Table 17 Class 3 or Class D-s3 d2 plastic rooflights limitations on use and boundary distance Table 17 Class 3 or Class D-s3 d2 plastic rooflights limitations on use and boundary distance
                                            • Table 18 TP a and TP b plastic rooflights limitations on use and boundary distance Table 18 TP a and TP b plastic rooflights limitations on use and boundary distance
                                            • Table 19 Fire and rescue service vehicle access to buildings excluding blocks of flats not fitted with fire mains Table 19 Fire and rescue service vehicle access to buildings excluding blocks of flats not fitted with fire mains
                                            • Table 20 Typical fire and rescue service vehicle access route specification Table 20 Typical fire and rescue service vehicle access route specification
                                            • Table A1 Specific provisions of test for fire resistance of elements of structure etc Table A1 Specific provisions of test for fire resistance of elements of structure etc
                                            • Table A1 continued Table A1 continued
                                            • Table A2 Minimum periods of fire resistance Table A2 Minimum periods of fire resistance
                                            • Table A3 Limitations on fire-protecting suspended ceilings - see Table A1 Note 4 Table A3 Limitations on fire-protecting suspended ceilings (see Table A1 Note 4)
                                            • Table A4 Limitations on the use of uninsulated glazed elements on escape routes Table A4 Limitations on the use of uninsulated glazed elements on escape routes]
                                            • Table A5 Notional designations of roof coverings Table A5 Notional designations of roof coverings
                                            • Table A6 Use and definitions of non-combustible materials Table A6 Use and definitions of non-combustible materials
                                            • Table A7 Use and definitions of materials of limited combustibility Table A7 Use and definitions of materials of limited combustibility
                                            • Table A8 Typical performance rating of some generic materials and products Table A8 Typical performance rating of some generic materials and products
                                            • Table B1 Provisions for fire doors Table B1 Provisions for fire doors
                                            • Table C1 Floor space factors Table C1 Floor space factors
                                            • Table D1 Classification of Purpose Groups Table D1 Classification of Purpose Groups
                                            • Table Maximum dimensions of building or compartment - non-residential buildings Table Maximum dimensions of building or compartment (non-residential buildings)